Data centre labels: where engraved lamacoids go and when to use them

Switchgear, UPS systems, PDUs, remote power panels, racks and EPO stations. Where engraved lamacoid labels go in a data centre, when a plate is the right call, and how to name the A and B sides so nobody opens the wrong breaker.

Guides7 min read
In short
  • A data centre is a chain of boxes: transfer switch, switchgear, UPS, PDU, remote power panel, rack. Every box in that chain needs a plate with its name and what feeds it.
  • Engraved lamacoids go on the equipment that stays put for the life of the room. Patch cords and ports keep their printed labels.
  • A side and B side should look different. One colour pair per side, used on every plate in that path.
  • Send the one-line names as a spreadsheet. We engrave the whole room in Burlington, the same day.

In a data hall, nobody wants to guess. The technician on a night shift with an approved change ticket has to open the right breaker on the right panel feeding the right rack, and leave the other power path alone. That only works if every piece of equipment between the utility and the server says what it is and where its power comes from. This post covers where lamacoid labels go in a data centre, when an engraved plate is the right call, and how to name the A and B sides so they can never be confused.

Two power paths to one rack, with a plate on every box The A side runs from transfer switch ATS-1 through switchgear SWGR-A, UPS-A, PDU-2A and remote power panel RPP-2A to power supply 1 in rack C07. The B side runs the same way through ATS-2, SWGR-B, UPS-B, PDU-2B and RPP-2B to power supply 2. Every box carries an engraved plate with its own name and the name of the box that feeds it. ONE NAME ON EVERY BOX IN THE CHAIN a dual-corded rack has two power paths; each box carries its own plate A SIDE B SIDE ATS-1SWGR-AUPS-APDU-2ARPP-2A auto transferswitchgearUPS systemPDU 600/208Vremote panel from UTIL+GENfrom ATS-1from SWGR-Afrom UPS-Afrom PDU-2A ATS-2SWGR-BUPS-BPDU-2BRPP-2B auto transferswitchgearUPS systemPDU 600/208Vremote panel from UTIL+GENfrom ATS-2from SWGR-Bfrom UPS-Bfrom PDU-2B RACK C07 PSU 1 ◂ A PSU 2 ◂ B dual-corded Trace any rack back to the utility by reading plates, not drawings. Example names. Use the site's own naming standard.
Two power paths, one rack. Every box from the transfer switch to the remote power panel carries its own name and the name of the box that feeds it, so the chain can be read on the floor.

01Why data centres label everything

A data centre is built so that one power path can be shut down for maintenance while the other keeps every server running. That design is only as safe as the labels. If a technician opens a breaker on what they believe is the B side and it turns out to feed the A side as well, redundancy is gone in one click.

So the rule in a well-run room is simple: every piece of electrical and mechanical equipment carries a permanent name, and every name matches the one-line drawing, the monitoring system and the maintenance procedure. Engraved lamacoids are how that name goes on the equipment. They are cut, not printed, so the name is the same on the last day of the lease as it was at commissioning.

02Where lamacoids go in a data centre

Walk a data hall and the electrical room behind it and you pass the same kinds of equipment over and over. Each one needs a plate.

A data hall floor plan with every plate location numbered Plan view of a data hall with four rows of racks in hot and cold aisles. Numbered markers show eight places that need engraved plates: cooling units on the wall, row-end plates, rack IDs, busway tap-off boxes, remote power panels at the row ends, PDUs along the wall, the emergency power off station and the room ID at the door. ONE DATA HALL, EIGHT KINDS OF PLATE plan view, not to scale COLD AISLE COLD AISLE HOT AISLE C07 ABCD CRAHCRAHCRAH RPP-2ARPP-2BRPP-2ARPP-2B PDU-2APDU-2B DATA HALL 2 1 2 3 4 5 6 7 8 12345678 Cooling unitsRow-end platesRack IDsBusway tap-off boxesRemote power panelsPDUsEPO stationRoom ID unit ID and the panel feeding itrow letter at both aisle endsgrid name, front and backcircuit and the rack it servesID, voltage, fed-fromID, in/out voltage, source UPSexactly what it shuts downat the door, matches drawings
One data hall, eight kinds of plate. The electrical room behind it adds switchgear, transfer switches, UPS systems, battery cabinets and generators.
SWGR-A MAIN

Switchgear and transfer switches

Section IDs, main and feeder breakers, and the transfer switches that pick between utility and generator. The plates people read before any switching.

UPS-A MOD 2

UPS systems and battery cabinets

UPS modules, bypass cabinets, maintenance bypass switches and battery strings. The bypass switch plate has to say exactly which way is safe.

PDU-2B

PDUs and remote power panels

Floor PDUs and the remote power panels at the row ends. Panel ID, voltage, and the box that feeds it, with breaker labels inside.

RACK C07

Racks and row ends

A grid name on the front and back of every rack, and a row letter at both ends of each aisle, so the rack in the ticket is the rack in front of you.

GEN-1 1500KW

Generators and fuel

Generator IDs, fuel tanks, day tanks and the load bank connection. Usually outdoors or in a hot room, so screw-mounted.

EPO DATA HALL 2

Emergency power off

The EPO station says exactly what it shuts down. It is the one plate where a vague name can take a whole room offline.

Add cooling: CRAH and CRAC units, chillers, pumps and the panels that feed them. Then the fire side: clean agent release stations and abort switches. Each one gets a name that matches the drawings.

03When an engraved plate is the right call

Not every label in a data centre should be a lamacoid. Patch cords, port numbers and cable ends change all the time, and printed labels made on site are the right tool for them. Engraved plates are for the things that stay put. Choose a lamacoid when:

  • The equipment will outlive the tenant. Switchgear, UPS systems, PDUs, panels and generators stay for decades. Their names should too.
  • Someone will switch power by reading it. Any plate a person reads before opening a breaker, transferring a load or pressing a button.
  • The spec calls for engraved nameplates. Data centre electrical specifications commonly call for engraved lamacoid nameplates on distribution equipment, and commissioning agents check them.
  • It has to match the one-line. Engraved names do not get handwritten corrections or a second sticker on top. What was approved is what is on the box.
  • The room runs hot or gets cleaned. Hot aisles, generator rooms and battery rooms are hard on adhesive and on printed film.
  • It is a safety control. EPO stations, bypass switches and fire release points get engraved plates in colours people recognise.

04A side and B side: make them look different

The single most useful labelling decision in a data centre is to give each power path its own colour pair and use it on every plate in that path, from the UPS to the rack strip. A technician then knows which side they are touching before they read a word.

A side and B side plates in two different colour pairs Left, the A side plates UPS-A, PDU-2A and RPP-2A in black with white letters. Right, the B side plates UPS-B, PDU-2B and RPP-2B in blue with white letters. In the middle, rack C07 has a black A power strip on one side and a blue B power strip on the other, matching the plates upstream. ONE COLOUR PAIR PER POWER PATH the same pair on every plate in that path, from UPS to rack strip A SIDE · BLACK/WHITE B SIDE · BLUE/WHITE UPS-APDU-2ARPP-2A UPS-BPDU-2BRPP-2B RACK C07 AB Never mix the pairs, and never use red for a side: red is for EPO, fire and danger. Example colours. If the owner has a standard, we match it exactly.
A side in Black/White, B side in Blue/White, down to the strips in the rack. The colours are an example; the rule is one pair per side, used everywhere.
  • Pick two pairs that read well side by side. Black/White and Blue/White, or White/Black and Black/White, are easy to tell apart in a dim hot aisle.
  • Keep red for safety. Red/White belongs to EPO stations, fire release points and danger plates. Using it for a power side dilutes the warning.
  • Put the side in the name as well as the colour. UPS-A, PDU-2A, RPP-2A. Colour helps people who see well in that light; the letter helps everyone else.
  • Follow the owner first. Colocation providers and large tenants often have a written colour standard. Send it with the order and we match it exactly.

05What goes on a data centre plate

Three things on every distribution plate: the equipment name, its rating, and where its power comes from. The name gets the biggest letters because it is what people search for from the aisle.

Anatomy of a remote power panel plate A 4 by 2 inch black plate with white engraved letters. The top line, RPP-2A, is the largest. The second line gives the rating, 208Y/120V 3PH 4W 225A. The third line gives the source, FED FROM PDU-2A / UPS-A. Four screw holes sit in the corners, clear of the text. NAME · RATING · SOURCE a remote power panel plate, about actual proportions RPP-2A 208Y/120V 3PH 4W 225A FED FROM PDU-2A / UPS-A 1 NAME2 RATING3 SOURCE4 HOLES largest; read from aislevoltage, phase, ampsthe box that feeds itcorners, clear of text 4 in2 in Example only. The wording comes from the approved drawings.
Name, rating, source. The name is the largest line because it is what people look for; the rating and source tell them what they are about to work on.
EquipmentExample plateTypical size
Switchgear sectionSWGR-A SECTION 3 / FED FROM ATS-14" × 2" or match the gear
Transfer switchATS-1 / NORMAL: UTILITY / EMERG: GEN-14" × 2"
UPS systemUPS-A / 600V IN / FEEDS PDU-1A, PDU-2A4" × 2"
Maintenance bypassUPS-A MAINT BYPASS / SEE PROCEDURE3" × 1.5"
Floor PDUPDU-2A / 600V-208Y/120V / FED FROM UPS-A4" × 2"
Remote power panelRPP-2A / 208Y/120V 225A / FED FROM PDU-2A4" × 2"
RackRACK C072" × 0.75", front and back
EPO stationEPO / DATA HALL 2 ONLY3" × 1", Red/White

For letter heights that read from a distance, see our lamacoid size guide. Inside the remote power panels, breaker and circuit labels follow the same approach as any panel; our post on electrical panel labels covers it.

06Data centre labelling facts worth knowing

  1. Redundancy depends on labels. A room built to keep running with one path down is only safe to maintain if people can tell the paths apart on the floor.
  2. Plates do not conduct. The engraving laminate is non-conductive, so a plate on a live panel or busway does not add anything to touch.
  3. The name should match three places. The one-line drawing, the monitoring system and the plate on the box. When they disagree, people stop trusting all three.
  4. Racks are usually named by floor grid. Many sites name cabinets by their floor-tile coordinates, in line with the TIA-606 administration standard, so the name tells you where to walk.
  5. Engraved names do not drift. Printed labels get reprinted, retyped and corrected over the years. An engraved plate keeps the name that was commissioned.
  6. Hot aisles are hard on glue. Exhaust air runs warm all day. Screw holes, or adhesive on a clean, cool surface, keep plates where they belong.
  7. Commissioning checks labels. Missing or wrong nameplates are a common punch-list item at turnover, and a whole room of them is quicker to fix in one order than one at a time.

07What to send when you order

DetailExample
Wording, one row per plateStraight from the one-line or the equipment schedule
Which side each plate is onA, B, or common, so we apply the right colour pair
Colour standardThe owner's or tenant's standard, or our suggestion
Size4" × 2" for distribution, 2" × 0.75" for racks, or match existing
MountingScrew holes, adhesive back, or both
Quantity per itemRack IDs front and back, row ends at both aisles

A data hall is a spreadsheet job. Export the equipment list, add a column for the side, and send it; our post on ordering from a spreadsheet shows how. For a handful of plates, design and price them in the Lamacoid Builder. Email lists to sales@llamacoids.ca. We engrave in Burlington, Ontario, the same day, and ship Canada-wide.

08Common questions

What labels does a data centre need?

Every piece of power and cooling equipment needs a permanent name that matches the drawings: switchgear, transfer switches, UPS systems, PDUs, remote power panels, generators, cooling units and EPO stations. Racks and row ends need location names. Patch cords and ports use printed labels.

Should data centre equipment labels be engraved?

For equipment that stays put, yes. Engraved lamacoids do not fade, peel or get reprinted with a different name, and data centre electrical specifications commonly call for engraved nameplates on distribution equipment.

How do you label A and B power in a data centre?

Put the side in the name, like UPS-A and PDU-2A, and give each side its own colour pair on every plate in that path. Keep red for EPO and safety plates. If the owner has a colour standard, follow it.

How should racks be labelled?

Name each rack by its floor-grid location and put the plate on the front and the back. Add a row-end plate at both ends of each aisle so people can find the row before the rack.

What should a PDU or RPP label say?

The equipment name, its voltage and rating, and the equipment that feeds it, for example RPP-2A / 208Y/120V 225A / FED FROM PDU-2A. Use the wording from the approved drawings.

Can you make labels for a whole data hall at once?

Yes. Send the equipment list as a spreadsheet with the wording, side and size for each plate. We engrave it in Burlington the same day and ship Canada-wide.